Error No. Error Type Error Point Main Reasons<br />

104*<br />

Master<br />

11 → 041<br />

Slave1<br />

12 → 042<br />

Slave2<br />

13 → 043<br />

Transmission Error<br />

Between Outdoors<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Master displays ODU number<br />

which is not communicated.<br />

Slave displays own error number<br />

■ Error Diagnosis and Countermeasure Flow Chart<br />

Is transmission<br />

cable installed<br />

normally?<br />

Yes<br />

Is Slave Unit Dip SW<br />

setting done?<br />

Yes<br />

Is main PCB power<br />

supplied?<br />

* Slave Unit Dip SW<br />

Slave1<br />

Slave2<br />

Slave3<br />

Yes<br />

Replace main PCB<br />

ON<br />

No<br />

No<br />

No<br />

1 2 3 4 5 6 7<br />

Connect transmission cable<br />

Dip SW setting<br />

Connect power cable<br />

ON<br />

1 2 3 4 5 6<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />

ON<br />

1 2 3 4 5 6 7<br />

ON<br />

1 2 3 4 5 6 7<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />

ON<br />

1 2 3 4 5 6 7<br />

ON<br />

1 2 3 4 5 6 7<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />

- 131 -<br />

Troubleshooting Guide<br />

1.Loose connection of power cable/transmission<br />

cable¿¸(Open/Short)<br />

2.Defect of each outdoor unit PCB<br />