Error No. Error Type Error Point Main Reasons<br />
104*<br />
Master<br />
11 → 041<br />
Slave1<br />
12 → 042<br />
Slave2<br />
13 → 043<br />
Transmission Error<br />
Between Outdoors<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
Master displays ODU number<br />
which is not communicated.<br />
Slave displays own error number<br />
■ Error Diagnosis and Countermeasure Flow Chart<br />
Is transmission<br />
cable installed<br />
normally?<br />
Yes<br />
Is Slave Unit Dip SW<br />
setting done?<br />
Yes<br />
Is main PCB power<br />
supplied?<br />
* Slave Unit Dip SW<br />
Slave1<br />
Slave2<br />
Slave3<br />
Yes<br />
Replace main PCB<br />
ON<br />
No<br />
No<br />
No<br />
1 2 3 4 5 6 7<br />
Connect transmission cable<br />
Dip SW setting<br />
Connect power cable<br />
ON<br />
1 2 3 4 5 6<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />
ON<br />
1 2 3 4 5 6 7<br />
ON<br />
1 2 3 4 5 6 7<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />
ON<br />
1 2 3 4 5 6 7<br />
ON<br />
1 2 3 4 5 6 7<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />
- 131 -<br />
Troubleshooting Guide<br />
1.Loose connection of power cable/transmission<br />
cable¿¸(Open/Short)<br />
2.Defect of each outdoor unit PCB<br />
<strong>LG</strong>E Internal Use Only