Function<br />

2.2 Defrost<br />

Defrost operation eliminates ice attached on heat exchanger, recovering performance of heat exchanger.<br />

Each cycle component operates as following table during defrost operation.<br />

Outdoor Unit<br />

Indoor Unit<br />

Component<br />

Inv Compressor<br />

Constant Speed Compressor<br />

FAN<br />

Main EEV<br />

Subcooling EEV<br />

4way valve<br />

Hot gas bypass valve<br />

Component<br />

Fan<br />

Thermo on unit EEV<br />

Thermo off unit EEV<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Starting<br />

25Hz<br />

OFF<br />

S<strong>to</strong>p<br />

Normal control<br />

Min. pulse<br />

On → OFF<br />

Normal control<br />

Starting<br />

OFF<br />

Normal control<br />

Min. pulse<br />

- 26 -<br />

Running<br />

Setting Value<br />

ON<br />

High pressure control<br />

Max. pulse<br />

Min. pulse<br />

OFF<br />

Normal control<br />

Running<br />

OFF<br />

1200 pulse<br />

1200 pulse<br />

■ Ending condition<br />

1) All heat exchanger pipe temperature are above 15°C(UY2) or 20°C(UW1) for 30 sec.<br />

2) The running time of defrost operation is over 30% of the <strong>to</strong>tal heating time<br />

3) If compressor protection control starts by high discharge temperature of compressor etc.<br />

Ending<br />

25Hz<br />

OFF<br />

50Hz<br />

200 pulse<br />

Min. pulse<br />

ON<br />

Normal control<br />

Ending<br />

OFF<br />

Normal control<br />

Min. pulse<br />