Function<br />

4.3 Sensor checking function<br />

Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or<br />

not. It checks 3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors.<br />

It is used for judging sensor abnormality. Note 2)<br />

Main PCB<br />

SW01S<br />

Main PCB<br />

SW01B<br />

SW02B<br />

Main PCB<br />

SW01V<br />

Main pcb<br />

LED<br />

Main PCB<br />

SW01V<br />

Start<br />

Wait for 3 min. after power<br />

reset<br />

Set the DIP switch according <strong>to</strong> the function<br />

Sensor Checking ➠ Refrigerant Au<strong>to</strong> Charging : 1,2,7 ON<br />

Sensor Checking ➠ Refrigerant Checking : 1,2,7,14 ON<br />

Would you perform<br />

the Sensor<br />

checking?<br />

Yes<br />

Press the black but<strong>to</strong>n for 2 sec. on main PCB.<br />

Indoor/Outdoor units operate with<br />

air circulation mode<br />

Judging sensor<br />

normality<br />

No<br />

Error Display<br />

Press the black but<strong>to</strong>n on the main PCB for 2 sec.<br />

Press the black but<strong>to</strong>n for 2 sec. after turning off all<br />

of SIP switch.<br />

Completed.<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Don’t Perform Sensor Checking<br />

No<br />

Note 3)<br />

Yes<br />

Note 4)<br />

- 34 -<br />

Note<br />

1. Sensor checking function is used with Refrigerant<br />

Checking and Refrigerant Au<strong>to</strong> Charging.<br />

2. Check abnormal sensor<br />

3. It is displayed at the LED on the main PCB at each step.<br />

4. Reference the sensor error in ** page.<br />

5. Refer <strong>to</strong> service manual about refrigerant au<strong>to</strong><br />

charging<br />

Caution<br />

1. Confirm au<strong>to</strong> addressing has been performed (Check<br />

installed number of IDU).<br />

2. The error can be displayed even if the sensor is<br />

normal according <strong>to</strong> installation and temperature<br />

condition. If error occurs, check the sensor and<br />

judge abnormality.<br />

Refrigerant Au<strong>to</strong> Charging<br />

Press the black but<strong>to</strong>n<br />

until '508' is displayed<br />

Refrigerant<br />

Au<strong>to</strong> Charging<br />

Refrigerant Checking<br />

Press the black but<strong>to</strong>n<br />

until '608' is displayed.<br />

Refrigerant<br />

Checking<br />

Note 1)<br />

<strong>LG</strong>E Internal Use Only