Function<br />
4.3 Sensor checking function<br />
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or<br />
not. It checks 3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors.<br />
It is used for judging sensor abnormality. Note 2)<br />
Main PCB<br />
SW01S<br />
Main PCB<br />
SW01B<br />
SW02B<br />
Main PCB<br />
SW01V<br />
Main pcb<br />
LED<br />
Main PCB<br />
SW01V<br />
Start<br />
Wait for 3 min. after power<br />
reset<br />
Set the DIP switch according <strong>to</strong> the function<br />
Sensor Checking ➠ Refrigerant Au<strong>to</strong> Charging : 1,2,7 ON<br />
Sensor Checking ➠ Refrigerant Checking : 1,2,7,14 ON<br />
Would you perform<br />
the Sensor<br />
checking?<br />
Yes<br />
Press the black but<strong>to</strong>n for 2 sec. on main PCB.<br />
Indoor/Outdoor units operate with<br />
air circulation mode<br />
Judging sensor<br />
normality<br />
No<br />
Error Display<br />
Press the black but<strong>to</strong>n on the main PCB for 2 sec.<br />
Press the black but<strong>to</strong>n for 2 sec. after turning off all<br />
of SIP switch.<br />
Completed.<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
Don’t Perform Sensor Checking<br />
No<br />
Note 3)<br />
Yes<br />
Note 4)<br />
- 34 -<br />
Note<br />
1. Sensor checking function is used with Refrigerant<br />
Checking and Refrigerant Au<strong>to</strong> Charging.<br />
2. Check abnormal sensor<br />
3. It is displayed at the LED on the main PCB at each step.<br />
4. Reference the sensor error in ** page.<br />
5. Refer <strong>to</strong> service manual about refrigerant au<strong>to</strong><br />
charging<br />
Caution<br />
1. Confirm au<strong>to</strong> addressing has been performed (Check<br />
installed number of IDU).<br />
2. The error can be displayed even if the sensor is<br />
normal according <strong>to</strong> installation and temperature<br />
condition. If error occurs, check the sensor and<br />
judge abnormality.<br />
Refrigerant Au<strong>to</strong> Charging<br />
Press the black but<strong>to</strong>n<br />
until '508' is displayed<br />
Refrigerant<br />
Au<strong>to</strong> Charging<br />
Refrigerant Checking<br />
Press the black but<strong>to</strong>n<br />
until '608' is displayed.<br />
Refrigerant<br />
Checking<br />
Note 1)<br />
<strong>LG</strong>E Internal Use Only