MAGNETIC FILTER<br />

> Determinating Conditioning No. 1<br />

To protect a new installation with chemical anticorrosive conditioning, a filter can be added to magnetically capture<br />

residues and to remove oxide particles that can cause failures at heat exchanger and other installation devices.<br />

Usage mode:<br />

- Very well knowledge <strong>of</strong> the installation (fabrication materials, when aluminium choose the appropriate product).<br />

- Choosing CLARIMAG filter and installation definition.<br />

- HYDROCHAUFF product intake through the filter.<br />

- At every check the <strong>pump</strong> must be activated and the impurities removed.<br />

The protection check will be done following the rules:<br />

- PH-value > 9,5;<br />

- Suspending matters – mg/l < 100;<br />

- Iron concentration mg/l < 0,5;<br />

- Copper concentration mg/l < 0,2;<br />

- Phosphates mg/l P2O5<br />

> 4.<br />

If necessary:<br />

- Sulfites > 20<br />

- TH °f < 5<br />

- TA °f > 5<br />

- TAC °f > 20<br />

A conditioned and controlled installation quarantees optimal and long-lasting functioning .<br />

> Determinating Conditioning No. 2<br />

In case <strong>of</strong> failures in functioning because <strong>of</strong> oxides and mud.<br />

Usage mode:<br />

- Well knowledge <strong>of</strong> the installation.<br />

- CLARIMAG filter choice and mounting.<br />

Curative conditioning for impurities removal<br />

- Injection <strong>of</strong> 1,2 to 1,5 l HYDROCHAUFF in a m³ water from the pipes.<br />

- Switch on the heating circuit and <strong>of</strong>ten check the oxide scale on the magnetic filter.<br />

- Constant removal <strong>of</strong> residues captured at the magnetic filter.<br />

- Restoring the product concentration according to the evacuated water quantity.<br />

- End <strong>of</strong> the curative treatment set by the following criteria : suspending elements < 100 mg/l.<br />

Preventive treatment:<br />

The HYDROCHAUFF dosis must always be between 1,2 and 1,5 l.<br />

The protection check will be done following the rules:<br />

- pH-value > 9,5;<br />

- Suspending matters – mg/l < 100;<br />

- Phosphate mg/l P 2O 5<br />

> 4;<br />

- Sulfite > 20<br />

- TH °f < 5<br />

- TA °f > 5<br />

- TAC °f > 20<br />