DESOXIDISING AND MUD REMOVAL PRODUCTS<br />
> Kit for the Desoxidising and Mud Removal <strong>of</strong> Central Heating<br />
Plants<br />
KIT DB Ref.7598<br />
Description:<br />
The DB Kit consists <strong>of</strong> 3 products:<br />
- 5 l DESOX<br />
- 2 l neutraliser<br />
- 2 l corrosion inhibitory agent<br />
In order to treat an installation with KIT DB depending on water<br />
quantity one must only inject the products according to their<br />
instructions.<br />
Preliminary condition:<br />
Before treatment any installation must be checked for deaeration system and for functionating valves.<br />
The total state <strong>of</strong> the installation must also be controlled in order to evaluate the leaking risks, but also to<br />
check internal and external pipe corrosion (when passing through walls and floors), radiators (environmental<br />
humidity), zones with bad circuit (also obstructions), tap or valve blocking, etc.<br />
Important:<br />
The treatment removes incrustation and suspending oxides and carbonates .<br />
The used products protect installation elements but water loss when removing mud by chemical treatment<br />
must be taken into account.<br />
Application mode:<br />
1. Complete evacuation <strong>of</strong> pipes<br />
2. Filling and introducing 5 l DESOX 80 for 100 l water.<br />
3. Checking if the product circulates through the installation by measuring the pH-value during the<br />
conditioning, must be about 1 for all radiators and fans.<br />
4. The installation must function for 48 hours.<br />
5. Check if the installation functions in all points.<br />
6. Complete evacuation <strong>of</strong> pipes after minimum 48 hours.<br />
7. Rinse the installation with cold water and manipulate the radiators’ taps in turn in order to obtain a<br />
preferred circuit and check the pH-value that must be around the neutralisation value (6-7).<br />
8. Refill the installation with 2 l neutraliser for 100 l water. Check the circuit. Check the pH-value, must be<br />
higher than 10. The solution must circulate for one hour at heat or cold.<br />
9. Evacuate and rinse (see No.7) until clean water flows and the pH-value becomes neutral.<br />
10. Refill and introduce 2 l protective corrosion inhibitory agent (Ref. Hydrochauff 920) that must remain in<br />
the installation. The control is done through the pH-value.<br />
In order to easily introduce the product use our manual injector.<br />
For a 60 – 100 l installation : one KIT DB<br />
For a 100 – 200 l installation : two KIT DB.<br />
25