TABLE 3.4<br />

PRODUCT MANUAL<br />

MINIMUM VERTICAL WALL REINFORCEMENT FOR 5½" [140mm] THICK FLAT ICF BASEMENT<br />

WALLS<br />

1,2,3,4,5<br />

Max. Wall<br />

Height<br />

(feet)<br />

8<br />

9<br />

10<br />

Maximum<br />

Unbalanced<br />

Backfill Height 6<br />

(feet)<br />

Maximum<br />

Equivalent Fluid<br />

Density<br />

30 pcf<br />

Minimum Vertical Reinforcement<br />

Maximum<br />

Equivalent Fluid<br />

Density<br />

45 pcf<br />

Maximum<br />

Equivalent Fluid<br />

Density<br />

60 pcf<br />

4 #4@48" #4@48" #4@48"<br />

5 #4@48"<br />

#3@12"; #4@22";<br />

#5@32"; #6@40"<br />

#3@8"; #4@14";<br />

#5@20"; #6@26"<br />

6<br />

#3@12"; #4@22";<br />

#5@30"; #6@40"<br />

#3@8"; #4@14";<br />

#5@20"; #6@24"<br />

#3@6"; #4@10";<br />

#5@14"; #6@20"<br />

7<br />

#3@8"; #4@14";<br />

#5@22"; #6@26"<br />

#3@5"; #4@10";<br />

#5@14"; #6@18"<br />

#3@4"; #4@6";<br />

#5@10"; #6@14"<br />

4 #4@48" #4@48" #4@48"<br />

5 #4@48"<br />

#3@12"; #4@20";<br />

#5@28"; #6@36"<br />

#3@8"; #4@14";<br />

#5@20"; #6@22"<br />

6<br />

#3@10"; #4@20";<br />

#5@28"; #6@34"<br />

#3@6"; #4@12";<br />

#5@18"; #6@20"<br />

#4@8";<br />

#5@14"; #6@16"<br />

7<br />

#3@8"; #4@14";<br />

#5@20"; #6@22"<br />

#4@8";<br />

#5@12"; #6@16"<br />

#4@6";<br />

#5@10"; #6@12"<br />

8<br />

#3@6"; #4@10";<br />

#5@14"; #6@16"<br />

#4@6";<br />

#5@10"; #6@12"<br />

#4@4";<br />

#5@6"; #6@8"<br />

4 #4@48" #4@48" #4@48"<br />

5 #4@48"<br />

#3@10"; #4@18";<br />

#5@26"; #6@30"<br />

#3@6"; #4@14";<br />

#5@18"; #6@20"<br />

6<br />

#3@10"; #4@18";<br />

#5@24"; #6@30"<br />

#3@6"; #4@12";<br />

#5@16"; #6@18"<br />

#3@4"; #4@8";<br />

#5@12"; #6@14"<br />

7<br />

#3@6"; #4@12";<br />

#5@16"; #6@18"<br />

#3@4"; #4@8";<br />

#5@12"<br />

#4@6";<br />

#5@8"; #6@10"<br />

8<br />

#3@4"; #4@8";<br />

#5@12"; #6@14"<br />

#4@6";<br />

#5@8"; #6@12"<br />

#4@4";<br />

#5@6"; #6@8"<br />

9<br />

#3@4"; #4@6";<br />

#5@10"; #6@12"<br />

#4@4";<br />

#5@6"; #6@8"<br />

#5@4"; #6@6"<br />

For SI: 1 foot = 0.3048 m; 1 inch = 25.4mm; 1 pcf = 16.0179 kg/m 3<br />

1<br />

Table values are based on reinforcing bars with a minimum yield strength of 40,000 psi [276 MPa] and concrete with a minimum<br />

specified compressive strength of 2,500 psi [17.2 MPa].<br />

2<br />

Spacing of rebar shall be permitted to be multiplied by 1.5 when reinforcing steel with a minimum yield strength of 60,000 psi [414 MPa]<br />

is used. Reinforcement shall not be less than one #4 bar at 48" [1.2 m] on center.<br />

3<br />

Deflection criterion is L/240, where L is the height of the basement wall in inches.<br />

4<br />

Interpolation shall not be permitted.<br />

5<br />

Walls shall be laterally supported at the top before backfilling.<br />

6<br />

Refer to Section 1.0 for the definition of unbalanced backfill height.<br />

Courtesy Portland Cement Association<br />

Page 164 Appendix B July 2009