GMBHFlow Meter | FC100-CAErrors6.2 Potential errorsIndependent of the priority group, all errors found are indicated with their relevant number.In order to facilitate operation, the last error is stored in a non-volatile memory. The stored error maybe retrieved and deleted in the main menu.If a combination of errors occurs simultaneously, they are indicated or stored in the error memoryobserving the following sequence.Priority group IError Cause RectificationNo. 1 No system parameter available Return to supplier.No. 2 Incorrect checksum of parameter Return to supplier.memoryNo. 3 Incorrect checksum of program Return to supplier.memoryNo. 4 Incorrect checksum of data memory Return to supplier.No. 5 Internal controller error Return to supplier.Priority group IIError Cause RectificationNo. 10 Sensor not connected; cable Check cable or replace sensor.between FC100-CA and sensoror sensor defectiveNo. 21Sensor selected (configurationmenu) differs from sensor connectedMedium temperature too highCorrect sensor selection inconfiguration menu60