User ManUal - FlowVision GmbH
User ManUal - FlowVision GmbH
User ManUal - FlowVision GmbH
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
GMBHFlow Meter | FC100-CATechnical Data7.4.2 Transistor outputs (DC)Pin selection: Signal name Pin XAH Polarity/ ERROR emitter 1 -/ ERROR collector 2 +/ BUSY / PULSE emitter 3 -/ BUSY / PULSE collector 4 +Limit Switch 2 emitter 5 -Limit Switch 2 collector 6 +Limit Switch 1 emitter 7 -Limit Switch 1 collector 8 +Voltage levelLow level - active:High level - passive:Reverse polarity protection:Short circuit protection:U ce < 0.8 V at I C < 10 mAU ce < 1 V at I C < 100 mAU ce < 48 VU ce max = 60 Vmax. leakage current ≤ 25 µAyesyesResistive loadMax. admissible switching capacity:Max. admissible switching current:Max. admissible switching voltage:1.5 W150 mA36 VInductive load - L < 100 mH(DC voltage - without external safety circuit)Max. admissible switching capacity:Max. admissible switching current:Max. admissible switching voltage:1.5 VA40 mA36 VCapacitive load - C < 20 µFMax. admissible switching capacity:Max. admissible switching current:Max. admissible switching voltage:Insulation voltage:1.5 VA1.5 A36 Vsignal contact - central electronic unit DC 500 Vsignal contact - signal contact DC 500 V66