GMBHFlow Meter | FC100-CATechnical Data7.3.1 Voltage output V1 - 5 V FSSignal voltage range:Accuracy:Resolution:Min. admissible load resistance:Max. admissible load capacity:Max. admissible load inductance:Short circuit proof:U S = 0 V (1 V) to 5 V± 0,75 % FS10 Bit (5 mV)R l = 1 kΩC l = 1 nFL l = 100 nHyes (XAO - between all terminals)7.3.2 Voltage output V2 - 10 V FSSignal voltage range:Accuracy:Resolution:Min. admissible load resistance:Max. admissible load capacity:Max. admissible load inductance:Short circuit proof:U S = 0 V (2 V) to 10 V± 0,75 % FS10 Bit (10 mV)R l = 2 kΩC l = 1 nFL l = 100 nHyes (XAO - between all terminals)7.3.3 Current output C1 - 20 mA FSSignal current range:Accuracy:Resolution:Min. admissible load resistance:Max. admissible load resistance:I S = 0 mA (4 mA) to 20 mA± 0,75 % FS10 Bit (20 µA)R l = 0 ΩR l = 300 Ω64