Wiring - control terminals<strong>Electric</strong>al characteristics for ATS<strong>22</strong>•••S6U range (110 Vac with 110 Vac logic inputs)Terminal Function CharacteristicsCL1CL2ATS<strong>22</strong> control power supply 110 Vac +10% -15%R1B Relay1 normally closedR1C Relay1 commonMax switching capability:5 A- 250 Vac or 30 Vdc on resistive load ( p.f. =1)R1A Relay1 normally open2 A-250 Vac or 30 Vdc on inductive load ( p.f.=0.4)R2B Relay2 normally closedMinimimal commutation capability:R2C Relay2 common100 mA 12 VdcR2A Relay2 normally openLI1 Logic input 1 3 x 110 V logic inputs with 20 kΩLI2 Logic input 2impedanceLI3 Logic input 3Umax = 121 Vac, Imax = 5 mANC Not connectedstate 1: U>79 V - I>2 mAstate 0: U