Command channelStatus wordThe Status register address is: 256• Use Function 3 only• Use Address_High (page) = 1• Use Address_Low = 0 (00H)• Read one register onlyBit Function Commentbit 0 ReadyAll the conditions that will permit the operation of a switching device by the remote host controller havebeen fulfilled.bit 1 OnThe main circuit contacts are closed or the semiconductor switches of semiconductor switching deviceare in the conducting state (ACC, DEC and BYPASS).bit 2 Trip A trip condition exists.bit 3 Warning A warning condition exists.bit 4 Reservedbit 5 LI3bit 6 LI2bit 7 LI1bit 8bit 9bit 10bit 11bit 12bit 13(Motor current in %)The motor current is expressed as a percentage of the motor rated current.Range is 0-200%.6 bits code200% = 63 (decimal) = 111111 (binary)bit 14 Local controlThe indication to a remote host controller that as a result of operator intervention, commands receivedwill not be accepted or acted upon (forced local command).bit 15 Ramping Accelerating or decelerating the motor.BBV51330 08/2012 67