Advanced settings menu (SEt2)Code Name/Description R/W Adjustment range Factory settingSEt2 (1)Advanced settings menuSEt2 allows you to have a 2nd set for the 5 parameters below.These parameters have the same definition as SEt.They can be validated with 2 possibilities:• Remotely by communication.• With logic input.t92 M 2nd initial voltage R/W 10..50 % of full voltageUln, by increment of 5ILt2Same as Initial voltage t90 page 51.M 2nd current limitSame as Current limit ILt page 51.R/W200..700 of In2 withmax 350% IcL30%350%ACC2 M 2nd acceleration time R/W 1..60 s 10 sSame as acceleration time ACC page 52.dEC2 M 2nd deceleration time R/W FrEE, 1..60 s FrEEIn2Same as deceleration time dEC page 52.M 2nd motor rated CurrentSame as motor rated current In page 50.R/W* 0.4 IcL up to IcL According to the softstarter rating (seepages 11 to <strong>22</strong>)(1)Only available when Advanced mode LAC page 50 is set to On.BBV51330 08/2012 55