Wiring - in line connection - application diagramATS<strong>22</strong>•••Q and ATS<strong>22</strong>•••S6: 230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control(1)Check the operating limits of the contact, for example when connecting to high rating contactors. See “<strong>Electric</strong>al characteristics” page 35.(2)Select a voltage transformer in accordance with the mains voltage.3-wire control settingIn the menu Advanced I/OIO, set the following parameters:Parameter Value DescriptionLI2 Strt Logic Input 2 is set to startr2 trlP Trip relay is de-energized upon trip38 BBV51330 08/2012