Advanced protections menu (PrO)Code Name/Description R/W Adjustment range Factory settingPrO (1)Advanced protections menuUId M Under current threshold R/W Off, 20..90 (%In) oFFTrips the soft starter when motor current drops below set level for a time longer than under current time delay (UIt).Active in running state.Note: Trip message is UCF.Current (A)UCFtrip messageTime (s)UIt M Under current time delay R/W 1..40 sby increment of 1 sOIdAdjusts the time delay linked with the parameter under current threshold UId.M Overcurrent thresholdR/W100..300 (%In)by increment of 5Trips the soft starter when motor current rises above a set level for a time longer than overcurrent time delay (OIt).Active in running state.Note: Trip message is OCF.Current (A)10 s200%Time (s)OCFTrip message(1)Only available when Advanced mode LAC page 50 is set to On.56 BBV51330 08/2012