Information system for the plant and would like to combine the data from all instruments<br />
into one program He has wntten a program In C-Ianguage for downloading data from the<br />
Panametrics He asked where IS the program from Panametncs for downloading data to<br />
a computer They use the flow meter every day for measunng hot water flow and mazut<br />
flow to bOilers<br />
They do not have a program diskette for the Enerac S N 11003252. They used to buy<br />
reference gases to calibrate Instruments In plant, but now calibrate the Enerac and use It<br />
to check other Instruments But they cannot use It to plot and analyze data on the pnnter<br />
as descnbed In the manual, and wonder If there IS special software to make it work We<br />
were given a document shOWing calculation of efficiency and energy savings of about<br />
$34,000 dunng 1995 using the Enerac We were also given a document from the Central<br />
Cnmean Regional De<strong>part</strong>ment of EnVironmental Protection regarding a dispute In<br />
companson of Inspector uSing coloremetnc burettes to test flu gas vs Enerac readings<br />
always being lower and a requirement to do parallel tests WIth the Donorgres Laboratory<br />
"TESTO-33" Instrument<br />
The Electrrcal De<strong>part</strong>ment has been uSing the Fluke power analyzer extensively to<br />
measure current, voltage and phase angles With very good results They measure voltage<br />
on busses, current on current transformers<br />
The accuracy of the Fluke IS higher than measurrng equipment In the plant for measunng<br />
voltage and current They trust the Instrument very much and use It to check other<br />
measunng Instruments When testing phases on a group of transformers at the gas<br />
turbines, they found an unbalance They could perform maintenance on the scheme, but<br />
the cost would be higher than the energy losses<br />
They used the Fluke to try to find the weak POints In bOiler feedwater pump motors and<br />
Identified that stator Winding need to be replaced They also discovered that copper rotor<br />
bars end connecttons were weakenrng, resulting in losses The problem IS that these are<br />
old 3 KV motors no longer made, as 6 KV IS standard<br />
They also found a small 200W unbalance of about 20% at admlnrstratlon bUilding where<br />
one phase was overloaded and they corrected It The Important lesson IS that the Fluke<br />
IS useful for Identifying energy losses<br />
The Infrared thermometer Mlnolta Cyclops IS used to check for heat losses from bOilers,<br />
drum insulation, steam lines, etc They found bad insulation on a stream drum and<br />
replaced It They tned to check the accuracy of Instrument against a thermocouple and<br />
found 40°C dIfference They do not trust the accuracy, but saId they do not have a manual<br />
in RUSSian or table of emissivitles We mentioned that the Mlkrom manual was translated<br />
and should be Similar<br />
They used the Instrument to find a steam leak under Insulation In the main bUIlding They<br />