Flexicom cx combination boiler - installation and service manual
Flexicom cx combination boiler - installation and service manual
Flexicom cx combination boiler - installation and service manual
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
10 Vertical Flue - Length, Preparation <strong>and</strong> InstallationCompletion of InstallationWith the flue terminal positioned in the roof the length of thefinal pipe can be determined. If a telescopic length cannotbe used, then a st<strong>and</strong>ard flue length can be cut to make thecorrect length. Cut the flue to the desired length measuringfrom the ‘O’ ring end <strong>and</strong> discard the plain end of the tube.The cuts must be square <strong>and</strong> made free of burrs to allowcorrect assembly.NOTE: The flue pipe is 10mm longer than the air pipe, seediagram 10.28.Carefully push the terminal assembly upwards to allow roomfor fitting the final flue piece. Fit a fixing bracket to the terminalassembly. Pull the terminal assembly down <strong>and</strong> join to the fluesystem. Ensure that the terminal is making a weather tightseal on the weather collar. Secure the fixing bracket fitted tothe terminal to the roofing struts or a purpose made batton.1298114853Diagram 10.261302312982Diagram 10.24Diagram 10.2712983Diagram 10.25Diagram 10.2832