242 <strong>Forensic</strong> Materials Engineering: Case Studies<br />

Partition<br />

Wall<br />

Bund Wall<br />

Overflow<br />

W 3<br />

Outside Wall<br />

Pipework<br />

Sight<br />

Tube<br />

Short<br />

Panel<br />

Compressor<br />

Equipment<br />

Caustic<br />

Jet<br />

Figure 7.27 Plan of caustic soda tank welded together from polypropylene<br />

panels to <strong>for</strong>m a 2.7-m-diameter tank. The jet of caustic soda emerged from the<br />

weld line of the lowest unrein<strong>for</strong>ced panel and crossed the bund wall intended<br />

to inhibit escape of fluid from the tank.<br />

small business manufacturing “dairy detergent.” 5,6 This detergent is a dilute<br />

solution of caustic soda to which various other chemicals are added to aid<br />

the cleansing effect when flushing out dairy equipment on farms, <strong>for</strong> example.<br />

Concentrated (40%) caustic soda is the basic raw material <strong>for</strong> the final<br />

product, and just four deliveries had been made to the factory when the<br />

failure occurred in late 1994. Each delivery involved complete filling of the<br />

tank by a full load.<br />

The failure <strong>for</strong>tunately occurred after the work shift had left <strong>for</strong> the day,<br />

and it was spotted by the production director, who was alone in the office<br />

above the factory floor. He heard a “bang” followed by the sound of “rain”<br />

and, looking out onto the factory floor, saw a jet of fluid shooting across the<br />

open space (Figure 7.27). The protective wall around the tank completely<br />

failed to constrict the fluid, which ran along the floor and into an adjacent<br />

unit that printed tachograph discs. Here the damage was extensive as specialist<br />

printing equipment was attacked and wrecked. The local fire deparment<br />

was called on to contain the fluid and prevent escape into the outer<br />

environment. Eventually a specialist recovery team company was hired to<br />

remove the fluid.<br />