<strong>CDA3000</strong> Operation Manual<br />

3 Installation<br />

Subject Projecting and installation regulations<br />

PE-terminal<br />

equipotential bonding<br />

Routing of cables<br />

Cable type<br />

Further hints for the<br />

control cabinet design<br />

Supplementary<br />

information<br />

Use a bright backing plate. Use cables and/or ground straps with<br />

cross sections as large as possible. Route the PE-terminal<br />

connection for the components in a star-shaped fashion and ensure<br />

large area contact of earthing (PE) and shielding connecting on the<br />

PE-bar of the backing plate to establish a low-resistance HFconnection.<br />

PE-mains connection in accordance with DIN VDE 0100 part 540<br />

Mains connection < 10 mm²<br />

Protective conductor cross-section min. 10 mm² or use 2<br />

conductors with a cross-section of the mains supply lines.<br />

Mains connection > 10 mm²:<br />

Use a protective conductor cross-section in compliance with<br />

the cross-section of the mains supply lines.<br />

Route the motor cable separated from signal and mains<br />

supply lines. The minimum distance between motor cable<br />

and signal line/mains line must be 20 cm, if necessary us<br />

separator.<br />

Always route the motor cable without interruptions and the<br />

shortest way out of the control cabinet.<br />

When using a motor contactor or a reactance control/motor<br />

filter, this should be directly mounted to the drive controller.<br />

Do not bare the core ends of the motor cable too soon.<br />

Avoid unnecessary cable lengths.<br />

The drive controllers must always be wired with screened motor<br />

cables and signal lines. A cable type with double copper braiding<br />

with 60 -70% coverage must be used for all screened connections.<br />

Contactors, relays, solenoid valves (switched inductivities)<br />

must be wired with fuses. The wiring must be directly<br />

connected to the respective coil.<br />

The switched inductivities should be at least 20 cm away<br />

from the process sontrolled assemblies.<br />

Place larger consumers near the supply.<br />

If possible enter signal lines only from one side.<br />

Lines of the same electric circuit must be twisted. Crosstalk<br />

is generally reduced by routing cables in close vicinity to<br />

earthed plates. Connect residual strands at both ends with<br />

the control cabinet ground (earth).<br />

Supplementary information can be found in the corresponding<br />

connection description<br />

Table 3.1 Projecting and installation regulations<br />