3.8 Control<br />

connections<br />

<strong>CDA3000</strong> Operation Manual<br />

3 Installation<br />

Step Action Comment<br />

1<br />

2<br />

Check whether your inverter module is<br />

fitted<br />

a modified software package<br />

(>V100.x)<br />

(standard software = Vx.xx-xx)<br />

If this is the case, the control terminal<br />

assignment is different. Please<br />

contact your project engineer with<br />

regard to wiring and commissioning!!<br />

Check whether you already have a<br />

SMARTCARD or a DRIVEMANAGER data<br />

set with a complete device setup.<br />

If this is the case, the control terminal<br />

assignment is different. Please<br />

contact your project engineer to obtain<br />

the terminal assignment!<br />

3 Choose a terminal assignment.<br />

4<br />

5<br />

Wire the control terminals with<br />

shielded cables.<br />

The only essential signals are the<br />

ENPO signals and a start signal<br />

(STR or STL).<br />

Keep all contacts open<br />

(inputs inactive).<br />

6 Check all connections again!<br />

Note the following points:<br />

3-13<br />

ANTRIEBSTECHNIK<br />

D- 35633 Lahnau<br />

Position of software name plate see<br />

section 3.1 Page 3-2<br />

Bulk customers<br />

Type: CDA32.004,C1.0<br />

Software: V 1xx.x<br />

CS:<br />

Data Set:<br />

C1D1<br />

SN.: 99120442<br />

For details of how to load the data<br />

set into the inverter module refer to<br />

section 4.6.<br />

see 3.8.1 “Choice of terminal<br />

assignment”<br />

Ground the cable shields over a<br />

wide area at both ends.<br />

Wire cross-section maximum<br />

1.5 mm² or two cores per terminal<br />

each 0.5 mm²<br />

Continue with commissioning in<br />

section 4.<br />

Always wire the control terminals with shielded cables.<br />

Lay the control cables separately from the mains lead and motor<br />

cable.<br />

The <strong>CDA3000</strong> Application Manual presents more drive solutions.<br />

For all shielded connections a cable type with double copper<br />

braiding with 60-70 % coverage must be used.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

A<br />

DE<br />

EN<br />

FR<br />

IT<br />

ES<br />

FR