Mains filter<br />
<strong>CDA3000</strong> Operation Manual<br />
3 Installation<br />
Attention: Danger to life! Never wire or disconnect electrical connections<br />
while they are live! Before working on the device disconnect<br />
the power. Wait until the DC-link voltage at terminals X1/<br />
RB+ and L- has fallen to the safety-low voltage before working<br />
on the device (approx. 5 minutes).<br />
Note the following points:<br />
Only all-current sensitive fault current breakers suitable for inverter<br />
operation may be used.<br />
Switching the mains power: Cyclic power switching is permitted<br />
every 60 seconds; jog mode is not permitted.<br />
− If switching is too frequent, the device protects itself by means<br />
of high-resistance isolation from the system.<br />
− After a rest phase of a few minutes the device is ready to start<br />
once again.<br />
TN network and TT network: Permitted without restriction.<br />
IT network (insulated center point): Not permitted!<br />
For details of measures to maintain UL approbation refer to<br />
Appendix A.8.<br />
Size Power range Mains filter<br />
BG1 ... 4 0.75 ... 7.5 <strong>kW</strong> Internal<br />
BG5 ... 8 11 ... <strong>132</strong> <strong>kW</strong> External1) 1) For supplementary components see <strong>CDA3000</strong> Order Catalogue.<br />
Note:<br />
Compliance with the limit curves (EN61800-3) to attenuate the lineborne<br />
interference voltage and the interference emitted from the inverter<br />
module depends on<br />
use of a line choke (recommended),<br />
the length of the motor cable and<br />
the preset clock frequency (4, 8 or 16 kHz) of the inverter module<br />
power stage.<br />
For further information please consult your project engineer.<br />