Wire cross-section<br />
<strong>CDA3000</strong> Operation Manual<br />
.<br />
<strong>Inverter</strong> module<br />
Device<br />
connected load<br />
[kVA]<br />
3 Installation<br />
Max. possible wire<br />
cross-section of<br />
terminals [mm²]<br />
3.6 DC network The inverter modules run in regenerative operation (braking) in a DC<br />
network feed power into the DC network which is consumed by the motordriven<br />
inverter modules.<br />
DC network operation of several inverter modules minimizes the power<br />
consumption from the mains and external braking resistors can be<br />
eliminated where appropriate.<br />
Note: It is essential that a DC network operation be checked at the<br />
project planning stage. Please consult your project engineer.<br />
3-11<br />
Recommended mains<br />
fusing (gL)<br />
[A]<br />
CDA32.004 1.7 2.5 1 x 10<br />
CDA32.006<br />
CDA32.008<br />
CDA34.003<br />
CDA34.005<br />
2.3<br />
3.0<br />
1.6<br />
3.0<br />
2.5<br />
1 x 16<br />
1 x 16<br />
3 x 10<br />
3 x 10<br />
CDA34.006 4.2 2.5 3 x 10<br />
CDA34.008<br />
CDA34.010<br />
CDA34.014<br />
CDA34.017<br />
CDA34.024<br />
CDA34.032<br />
CDA34.045<br />
CDA34.060<br />
CDA34.072<br />
CDA34.090<br />
CDA34.110<br />
CDA34.143<br />
CDA34.170<br />
CDA34.250<br />
5.7<br />
7.3<br />
10.2<br />
12.4<br />
17.5<br />
23.3<br />
32.8<br />
43.8<br />
52<br />
65<br />
80<br />
104<br />
124<br />
145<br />
173<br />
2.5<br />
4.0<br />
10<br />
25<br />
50<br />
Threaded bolt M8<br />
Threaded bolt M8<br />
3 x 10<br />
3 x 16<br />
3 x 20<br />
3 x 25<br />
3 x 35<br />
3 x 50<br />
3 x 50<br />
3 x 63<br />
3 x 80<br />
3 x 100<br />
3 x 125<br />
3 x 160<br />
3 x 200<br />
3 x 250<br />
3 x 315<br />
Table 3.2 Wire cross-sections and mains fuses (VDE0298 must be<br />
observed)<br />