Set lines per revolution of<br />
encoder used<br />
4. Change basic settings...<br />
<strong>CDA3000</strong> Operation Manual<br />
4 Commissioning<br />
This setting is only required in “FOR” mode.<br />
In the last step you can adapt the<br />
basic setting of the preset solution<br />
to your application.<br />
The setting options vary according<br />
to the selected preset drive<br />
solution (here the example for<br />
ROT_2).<br />
Test setting<br />
Attention: Make sure that the rotating drive of your machine cannot<br />
cause any damage during commissioning (such as by<br />
overshooting a stop limit) and that there are no personnel<br />
inside the danger zone.<br />
Step Action Note<br />
1 Close ENPO contact. ENPO active enables power stage.<br />
2 Set low reference with R1.<br />
see section “3.8.5 Terminal<br />
assignment 3”<br />
3<br />
Start drive by closing STL or STR<br />
contact.<br />
Motor accelerates to preset reference<br />
4<br />
If the motor runs uncontrolled and does<br />
Check phase position, motor and<br />
not accelerate up to the preset<br />
encoder connections, see section 4.5<br />
reference, stop the drive (open STL or<br />
“Direction check”<br />
STR contact).<br />
Motor accelerates up to preset<br />
reference, commissioning can be<br />
continued.<br />
5 Set correction reference with R2<br />
<strong>Drive</strong> accelerates further by amount<br />
of correction reference.<br />
4-9<br />