A.6 through use of a<br />

line choke<br />

<strong>CDA3000</strong> Operation Manual<br />

Example for the digital output OSD01:<br />

f [Hz]<br />

STR (Start/Stop)<br />

1<br />

0<br />

e.g. OSD01 (ENMO) 1<br />

0<br />

power stage<br />

0<br />

1<br />

0<br />

Attention: A corresponding driver relay has to be used between the<br />

digital output and the motor contactor.<br />

Line chokes are required:<br />

TENMO TENMO<br />

Where the drive controller is used in applications with disturbance<br />

variables corresponding to environment class 3, as per<br />

EN 61000-2-4 and above (hostile industrial environment).<br />

With a dc-link between multiple inverter moduls.<br />

Characteristics of environment class 3 include:<br />

Mains voltage fluctuations > + 10% UN Short-time interruptions between 10 ms and 60 s<br />

Voltage asymmetry > 3%<br />

Environment class 3 typically applies where:<br />

a major part of the load is supplied by power converters (dc choppers<br />

or soft-start equipment).<br />

welding machines are present.<br />

induction or arc furnaces are present.<br />

large motors are started frequently.<br />

loads fluctuate rapidly.<br />

A-12<br />