D CDA3000 Inverter Drive System 750 W - 132 kW - Igor Chudov
D CDA3000 Inverter Drive System 750 W - 132 kW - Igor Chudov
D CDA3000 Inverter Drive System 750 W - 132 kW - Igor Chudov
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
A.6 through use of a<br />
line choke<br />
<strong>CDA3000</strong> Operation Manual<br />
Example for the digital output OSD01:<br />
f [Hz]<br />
STR (Start/Stop)<br />
1<br />
0<br />
e.g. OSD01 (ENMO) 1<br />
0<br />
power stage<br />
0<br />
1<br />
0<br />
Attention: A corresponding driver relay has to be used between the<br />
digital output and the motor contactor.<br />
Line chokes are required:<br />
TENMO TENMO<br />
Where the drive controller is used in applications with disturbance<br />
variables corresponding to environment class 3, as per<br />
EN 61000-2-4 and above (hostile industrial environment).<br />
With a dc-link between multiple inverter moduls.<br />
Characteristics of environment class 3 include:<br />
Mains voltage fluctuations > + 10% UN Short-time interruptions between 10 ms and 60 s<br />
Voltage asymmetry > 3%<br />
Environment class 3 typically applies where:<br />
a major part of the load is supplied by power converters (dc choppers<br />
or soft-start equipment).<br />
welding machines are present.<br />
induction or arc furnaces are present.<br />
large motors are started frequently.<br />
loads fluctuate rapidly.<br />
A-12<br />
t