3.8.2 Specification of<br />

control<br />

terminals<br />

The terminal scan<br />

cycle is 1 ms.<br />

<strong>CDA3000</strong> Operation Manual<br />

Analog<br />

inputs<br />

Analog<br />

output<br />

Digital<br />

inputs<br />

Digital<br />

outputs<br />

Relay<br />

output<br />

Motor<br />

temperature<br />

Voltage<br />

supply<br />

3 Installation<br />

Des. Specification<br />

ISA00<br />

ISA01<br />

ISA00: U IN = +10 V DC, ±10 V DC, I IN = (0) 4-20 mA DC,<br />

switchable by software<br />

ISA01: U IN = +10 V DC<br />

Tolerance U: ± 1% v. M., I: ±1% of MV<br />

24 V digital input, PLC-compatible<br />

Switching level Low/High: 8 V DC<br />

Resolution 10-bit<br />

R in=110kΩ<br />

Floating against digital ground<br />

OSA00 Tolerance U: ±2.5% of MV<br />

U out=+10 V DC, R OUT=100 Ω<br />

I max =5 mA, short-circuit-proof<br />

ISD00<br />

ISD01<br />

ISD02<br />

ISD03<br />

PLC-compatible<br />

Switching level Low/High: 18* V DC<br />

I max at 24 V = 10 mA<br />

R IN = 3 kΩ<br />

ENPO Power stage enable = High level<br />

Specification as ISDxx<br />

OSD00 Short-circuit-proof<br />

PLC-compatible<br />

Imax = 50 mA<br />

Protection against inductive load<br />

High-side driver<br />

OSD01 Short-circuit-proof with 24V supply from inverter module<br />

PLC-compatible<br />

Imax = 50mA<br />

No internal freewheeling diode; provide external protection<br />

High-side driver<br />

OSD02 Relay 48 V / 1 A AC, changeover contact<br />

Usage category AC1<br />

Operating delay approx. 10 ms<br />

PTC1/ 2 max. 12 V DC, measuring range 100 Ω - 15 kΩ<br />

Suitable for PTC to DIN 44082 or temperature sensor KTY84-130<br />

(tolerance band yellow) or thermostatic circuit-breaker<br />

+10.5V Reference voltage U R =10.5 V DC, short-circuit-proof<br />

I max = 5 mA<br />

+24V Auxiliary voltage UV = 24 V DC, short-circuit-proof<br />

Imax = 200 mA (overall, also includes driver currents for outputs<br />

OSD0x)<br />

*In the range >5 V /