Error message<br />
Main index Subindex<br />
11<br />
12<br />
Error message explanation Measures<br />
0 Homing: Error at start No controller enabling.<br />
1 Error during homing Homing has been interrupted, for example<br />
because the controller is no longer enabled.<br />
2 Homing: Reset pulse error The necessary index pulse is missing<br />
3 Homing: Timeout The maximum time parameterized for homing<br />
has been reached before the homing run could<br />
be completed.<br />
4 Homing:<br />
Wrong/invalid limit switch<br />
The associated limit switch is not connected.<br />
Limit switches mixed up?<br />
5 Homing: I²t / lag error Unsuitable parameterization of acceleration<br />
ramps.<br />
Invalid stop reached, e.g. because no homing<br />
switch is connected.<br />
Contact the technical support team.<br />
6 Homing:<br />
End of search path<br />
0 CAN bus:<br />
Double node number<br />
1 CAN communication error:<br />
Bus Off<br />
2 CAN communication error during<br />
transmission<br />
3 CAN communication error during<br />
reception<br />
The maximum homing distance has been<br />
travelled but the reference point of the<br />
destination of the homing run have not been<br />
reached.<br />
Check the configuration of the devices<br />
connected to the CAN bus.<br />
The CAN chip has switched off the<br />
communication due to communication errors<br />
(BUS OFF).<br />
The signals are disturbed during the<br />
transmission of messages.<br />
The signals are disturbed during the reception<br />
of messages.<br />
9 CAN: Protocol error Check the command syntax of the control<br />
(record the data traffic).<br />
13 0 CAN bus: Timeout Check CAN parameterization<br />
E 732 GB 129<br />