KUHNKE Automation <strong>Fuxx</strong> <strong>Control</strong> <strong>ARS</strong> <strong>2320</strong> / <strong>ARS</strong> <strong>2340</strong><br />

Table 47: Technical data: PROFIBUS-DP interface: Interfaces and communication<br />

Communication interface Profibus module<br />

<strong>Control</strong>ler Profibus controller VPC3+, 12 Mbaud max.<br />

Protocol Profibus DP,<br />

32-byte telegrams with operating-mode-depending configuration<br />

Interface Floating, D-SUB 9-pin, integrated bus terminating resistors<br />

Special functions Support of diagnosis data, RTS signal led out, fail-safe mode, sync/freeze<br />

The following elements can be found on the front plate of the PROFIBUS-DP interface (see Figure<br />

34):<br />

� a green LED to indicate readiness for operation<br />

� a 9-pin female DSUB connector<br />

� two DIP switches for activating the terminating resistors<br />

Figure 34: PROFIBUS-DP interface: Front view<br />