KUHNKE Automation <strong>Fuxx</strong> <strong>Control</strong> <strong>ARS</strong> <strong>2320</strong> / <strong>ARS</strong> <strong>2340</strong><br />
For highly flexible applications:<br />
� LAPP KABEL UNITRONIC BUS-FD P L2/FIP; 1 x 2 x 0.64; ∅ 8 mm,<br />
with tinned CU shielding<br />
for highly flexible use in drag chains<br />
11.1.4 Termination and bus terminating resistors<br />
Every bus segment of a PROFIBUS network has to be equipped with bus terminating resistors to<br />
minimise line reflections and to adjust a defined rest potential on the line. The bus termination has to<br />
be provided at the beginning and at the end of every bus segment.<br />
Most PROFIBUS connectors come supplied with integrated terminating resistors. For bus connections<br />
with connectors without integrated terminating resistors, the PROFIBUS-DP interface has its own<br />
terminating resistors. They can be activated with the help of the two DIP switches on the module<br />
(switch set to ON).<br />
To ensure safe operation of the network, only one bus termination may be used at a time.<br />
The external connection can also be set up discretely (see Figure 35). The power supply of 5 V<br />
required for the externally connected terminating resistors is supplied at the PROFIBUS connector of<br />
the PROFIBUS-DP interface (see pin assignment in Table 48).<br />
GND 5V<br />
390 Ohm<br />
220 Ohm<br />
390 Ohm<br />
+5V<br />
B-Line<br />
A-Line<br />
Figure 35: PROFIBUS-DP interface: Connection with external terminating resistors<br />
E 732 GB 139<br />
14.12.2006