<strong>Fuxx</strong> <strong>Control</strong> <strong>ARS</strong> <strong>2320</strong> / <strong>ARS</strong> <strong>2340</strong> KUHNKE Automation<br />
5.2.3 Setpoint management<br />
The setpoint for the torque and speed control modes can be set via a setpoint management system.<br />
The following setpoint sources can be selected:<br />
� 3 analog inputs:<br />
� AIN 0, AIN 1 and AIN 2<br />
� 3 fixed values:<br />
� 1 st value: Setting depending on controller enabling logic:<br />
� Fixed value 1 or<br />
� RS232 interface or<br />
� CANopen bus interface or<br />
� PROFIBUS-DP interface or<br />
� SERCOS interface <br />
� 2 nd and 3 rd value: Setting of fixed values 2 and 3<br />
� Process controller <br />
� SYNC input <br />
� Additional incremental encoder input [X10] <br />
If no setpoint source is active, the setpoint is zero.<br />
The setpoint management system has a ramp generator with a preceding adder. Any of the abovementioned<br />
setpoint sources can be selected using corresponding selectors and run through the ramp<br />
generator. Additional setpoint sources, which are not run through the ramp generator, can be selected<br />
with the help of two additional selectors. The total setpoint is a summation of all values. The<br />
acceleration and braking time of the ramp can be parameterized depending on the direction.<br />
5.2.4 Torque-controlled mode<br />
In torque-controlled mode, a certain torque is preset and generated in the motor by the servo<br />
controller. In this case, only the current controller is activated since the torque is proportional to the<br />
motor current.<br />