1.01<br />

1.005<br />

PSCAD/EMTDC<br />

Modelo Tensorial<br />

Modelo Convencional<br />

Tensão (pu)<br />

1<br />

0.995<br />

0.99<br />

0 0.05 0.1 0.15 0.2 0.25 0.3<br />

Tempo (s)<br />

(a)<br />

1.01<br />

1.005<br />

PSCAD/EMTDC<br />

Modelo Tensorial<br />

Modelo Convencional<br />

Tensão (pu)<br />

1<br />

0.995<br />

0.99<br />

0 0.05 0.1 0.15 0.2 0.25 0.3<br />

Tempo (s)<br />

(b)<br />

Figura 4.10.3 – Tensão rms filtrada do <strong>SVC</strong> 1 (a) e do <strong>SVC</strong> 2 (b) para perturbação em degrau na tensão<br />

da fonte e ganhos de K p = 0.25 e K i = 500s -1 .<br />

A Figura 4.10.4 apresenta as simulações para uma perturbação em degrau de 1% na<br />

tensão de referência do <strong>SVC</strong> 1, utilizando os ganhos K p = 0,1 e K i = 200s -1 para ambos<br />

os <strong>SVC</strong>s. Na Figura 4.10.5 o ganho utilizado foi de K p = 0,4 e K i = 800s -1 para ambos os<br />

<strong>SVC</strong>s. Nestas figuras fica claro que o modelo convencional não apresenta bons<br />

resultados fora da faixa de ganhos para o qual foi sintonizado, particularmente quando<br />

186