10.04.2013 Views

The Turbo Air® 3000 Centrifugal Compressor Compressor Handbook

The Turbo Air® 3000 Centrifugal Compressor Compressor Handbook

The Turbo Air® 3000 Centrifugal Compressor Compressor Handbook

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>The</strong> <strong>Turbo</strong> Air <strong>3000</strong> <strong>Centrifugal</strong> <strong>Compressor</strong> Operator’s Manual<br />

Block Valve<br />

All compressor installations must include a block valve to insulate the compressor from the remainder of<br />

the pressure system in case of a check valve failure. <strong>The</strong> user must supply the block valve, which must<br />

be installed after the check valve.<br />

A—16<br />

WARNING:<br />

Whenever the compressor is being serviced, be certain to close and lock the block valve.<br />

<strong>The</strong>se measures are necessary to protect the compressor whenever the check valve is being<br />

serviced or otherwise not functional.<br />

Automatic Block Valve Option<br />

<strong>The</strong> Automatic Block Valve option fits between two 150-lb. ANSI raised-face flanges in the discharge air<br />

piping. <strong>The</strong> recommended installation is after the aftercooler (if so equipped) and at least four pipe<br />

lengths beyond the discharge check valve. While the valve orientation is at the installer’s discretion,<br />

accessibility should be considered if the Automatic Block Valve is to be used as a lockout device during<br />

compressor service.<br />

<strong>The</strong> valve actuator requires a 60-psig air supply for a three-stage compressor or a 30-psig air supply for<br />

a two-stage compressor. If available, use the instrument air supply; alternatively, tap the pipe located<br />

immediately upstream of the valve itself. <strong>The</strong> supply air should be connected to the lockout valve on<br />

the block valve assembly. Verify correct operation of the Automatic Block Valve at the initial startup,<br />

since valve malfunction may cause compressor surging. Refer to Cooper <strong>Turbo</strong>compressor EDR-A-008,<br />

Automatic Block Valve, for additional information on the Automatic Block Valve option.<br />

Control Valve Piping<br />

Depending on the control method being applied, the <strong>Turbo</strong> Air <strong>3000</strong> will either completely or partially<br />

unload whenever the capacity of the compressor exceeds the compressed air system’s demand. Under<br />

AUTO-OFFLINE control, the compressor is unloaded by completely bypassing the compressed air system<br />

and venting discharge air back to the inlet of the compressor or out to atmosphere. In other cases, a<br />

portion of the discharge air is partially vented or blown-off in order to maintain Constant Pressure or<br />

constant mass flow into the compressed air system.<br />

Bypass Valve<br />

<strong>The</strong> AUTO-OFFLINE Control method utilizes a pop-action bypass valve (BPV). <strong>The</strong> BPV operates in either a<br />

fully open or fully closed position. <strong>The</strong> compressor owner/installer is responsible for the proper installation<br />

of this control valve (which is shipped separately) unless the Mounted Bypass Valve option is<br />

purchased. (Refer to the relevant heading for additional information about that option.)<br />

Modulating Blow-Off Valve (MBOV)<br />

All control methods may utilize a modulating blow-off valve (MBOV) which operates in any position<br />

from fully closed to fully open. A pneumatic actuator, and I/P transducer, a volume booster and a filter<br />

regulator all come mounted and integrally piped to the valve body as a complete assembly. <strong>The</strong> owner/<br />

installer is responsible for the proper installation of the MBOV, which is shipped separately.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!