Routine Startup—Local Control<br />
Use this procedure to start the compressor locally from the User Interface Module (UIM).<br />
Routine Operation<br />
WARNING<br />
Only fully trained personnel should be allowed to start and operate this compressor.<br />
Failure to comply may result in serious injury or death.<br />
1. Close the condensate drain bypass valves.<br />
2. Turn on the cooling water supply. (May occur automatically as part of start sequence.)<br />
3. Check the oil level in the oil reservoir.<br />
4. Activate the oil reservoir vent system (air-powered ejector, or electric-powered vacuum pump),<br />
and adjust appropriately.<br />
5. Rack in the main drive motor starter disconnect.<br />
6. Inspect the compressor for any water or oil leaks.<br />
7. Open the discharge air system block valve. (May occur automatically as part of start sequence.)<br />
CAUTION:<br />
Do not open the air system block valve when the oil pump is not operating. Operation<br />
under such conditions may cause compressor damage.<br />
8. Press the START key on the Vantage Control Panel and observe the compressor start sequence.<br />
A screen appears similar to the screen shown below.<br />
Starting<br />
Description Status<br />
1. Oil Pressure > 100.0 PSI Complete<br />
2. Oil Temperature > 70 Waiting 2<br />
3. Discharge Pressure < 5 PSI<br />
4. Checking Water Flow = ON<br />
5. Motor Enable = ON<br />
6. Start Signal = 8.00<br />
(This is sample screen that may contain extra messages.)<br />
9. After startup, control defaults to the Auto mode. Press Home to observe selected processes<br />
and verify stability. To stop the Auto mode, press Unload.<br />
4—5