Installation<br />
CAUTION:<br />
When fabricating the coolant supply piping (Figure A—11), always install the throttle<br />
valve on the discharge side of the manifold rather than the inlet side. This will ensure that<br />
the coolers are always flooded and that no air locks will form to restrict flow.<br />
After fabrication of the cooling water piping is complete and before the initial compressor startup,<br />
install temporary filter screens in the supply lines just before entry to the heat exchangers. Flush the<br />
pipes thoroughly, and when it is determined that the supply piping is completely free of any foreign<br />
matter, remove the screens. Reconnect the compressor manifold, and verify that there are no external<br />
leaks. To verify that there are no internal leaks, open the condensate drains of the intercoolers and<br />
aftercooler.<br />
3” Victaulic Connection<br />
Figure A—11. Typical Water Supply and Return Piping<br />
E<br />
C<br />
D<br />
A<br />
B<br />
C<br />
A<br />
B<br />
A. Temperature Gauge<br />
B. Pressure Gauge<br />
C. Shut-Off Valve<br />
D. Throttle Valve<br />
E. Drain Connection<br />
A—21