<strong>The</strong> <strong>Turbo</strong> Air <strong>3000</strong> <strong>Centrifugal</strong> <strong>Compressor</strong> <strong>Handbook</strong><br />

Auto-Offline Control<br />

Inlet Valve Control<br />

When the actual system pressure is lower than the System Pressure Setpoint, the Vantage controller<br />

begins to load the compressor. During the initial load cycle, the inlet valve opens to a Minimum Flow<br />

value when the compressor discharge valve begins closing.<br />

During this initial load cycle, the Inlet Maximum Load control loop controls the inlet valve and quickly<br />

loads the compressor within the Maximum Motor Load setpoint constraints.<br />

Note: <strong>The</strong> proper Motor Load setting for 1.15 service factor motors is 112% of motor full<br />

load amps (FLA).<br />

As the system air pressure approaches the System Pressure setpoint, the Inlet System Pressure control<br />

loop obtains control of the inlet valve (if the motor amps are below maximum).<br />

In cases of low air demand, Inlet System Pressure control loop maintains the System Pressure setpoint<br />

by reducing the compressor output through inlet valve throttling moves. This throttling continues<br />

until the compressor reaches its minimum stable operating point, and the Inlet Minimum Flow control<br />

loop resumes automatic control of the inlet valve.<br />

In the Minimum Flow control loop, the inlet valve is controlled along the minimum flow Surge Control<br />

Offset line, a user-set specific offset along the entire actual surge curve.<br />

An important aspect of the Minimum Flow control loop, is that the actual system pressure is allowed<br />

to increase above the System Pressure setpoint, to the System Pressure Offset setpoint. When the<br />

measured pressure reaches the System Pressure Offset value, Auto-Offline then smoothly transfers<br />

control to the compressor discharge valve control loops.<br />

C—8