Bend, DI, Epoxy lined (FL x FL)<br />

<strong>Material</strong> Item Approved for Use In:<br />

Water System:<br />

Wastewater System:<br />

Reclaimed Water System:<br />

Approved Manufacturers:<br />

Manufacturer's Name: Model/Series #:<br />

Open Market<br />

<strong>Material</strong> Description:<br />

Fitting shall be ceramic epoxy-lined (Protecto<br />

401) ductile iron coated on exterior with a<br />

1-mil asphaltic seal coating. Fitting exterior<br />

shall be marked to indicate "Epoxy Lined - 40<br />

mils minimum, P401". Flanges shall be pressure<br />

rated to a minimum of 250 psi working pressure.<br />

Application:<br />

For use in wastewater systems.<br />

See Appendix B for Installation Instructions<br />

Pictures are for Illustrative Purposes Only<br />

GRU Stock Information:<br />

BEND, EPOXY LINED<br />

Stock Number Stock Description<br />

000165654 4" x 45 deg<br />

000165603 4" x 90 deg<br />

000165808 6" x 45 deg<br />

000165751 6" x 90 deg<br />

000165956 8" x 45 deg<br />

000165905 8" x 90 deg<br />

'For GRU use only: An X indicates item is stockless<br />

ASTM A536 - DI Castings<br />

AWWA C104 - Lining<br />

AWWA C110 - DI Fittings<br />

AWWA C153 - DI Fittings<br />

NSF 61 - Potable Water<br />

National <strong>Standards</strong>:<br />

See Appendix A for Full Description of <strong>Standards</strong><br />

Water, Wastewater and Reclaimed Water<br />

<strong>Material</strong> <strong>Standards</strong><br />