20.04.2014 Views

SVI-II Instruc Man.book - Fagerberg

SVI-II Instruc Man.book - Fagerberg

SVI-II Instruc Man.book - Fagerberg

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Masoneilan Dresser<br />

<strong>SVI</strong> <strong>II</strong> AP <strong>Instruc</strong>tion <strong>Man</strong>ual<br />

Physical<br />

Inspection<br />

<strong>SVI</strong> <strong>II</strong> AP checkout consists of physical and operational checkout procedures.<br />

The physical checkout procedures are listed below:<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Inspect the Actuator, Linkages, or Rotary Adapter<br />

Verify the Mounting and Linkage Adjustment<br />

Check the Magnet<br />

Check the Air Supply<br />

Check the Electronic Module Connections<br />

Valve Mounting<br />

The Air Supply<br />

Actuator, Linkages, or Rotary Adapter<br />

Verify that the mounting has not been damaged in shipment for a<br />

pre-mounted <strong>SVI</strong> <strong>II</strong> AP, physically inspect the actuator, linkage. Record the<br />

following information for the configuration checkout:<br />

1. Valve Air to Open (ATO) or<br />

2. Air to Close (ATC)<br />

3. Actuator pressure rating<br />

4. Actuator bench range<br />

5. Inherent trim characteristic of the control valve; linear, equal<br />

percentage, or other.<br />

Note:<br />

Refer to the valve data sheet or model number of control valve.<br />

Verify Mounting and Linkage Adjustment<br />

Checking the Magnet<br />

<br />

<br />

Performing a Visual Inspection<br />

Inspect the mounting and make any needed adjustments before running the<br />

positioner and checking the digital configuration.<br />

There are two methods of checking the <strong>SVI</strong> <strong>II</strong> AP magnet:<br />

Perform a visual inspection<br />

Use ValVue 2.4 to check the magnet<br />

You must remove the positioner from the bracket to visually inspect the<br />

magnet orientation.<br />

For rotary valves, such as a Camflex, or for actuators with rotation of less than<br />

60 degrees, the magnet assembly must be aligned as shown in Figure 17 on<br />

page 31.<br />

For rotary valves, or for actuators with rotations greater than 60 degrees, the<br />

magnet assembly must be aligned as shown in Figure 18 on page 31.<br />

Note:<br />

For a reciprocating valve, it is not necessary to remove the positioner<br />

to visually inspect the magnet setting and linkage of a reciprocating<br />

valve.<br />