Masoneilan Dresser<br />

<strong>SVI</strong> <strong>II</strong> AP <strong>Instruc</strong>tion <strong>Man</strong>ual<br />

VIEW ERR Diagnostics Messages<br />

Diagnostic messages are viewed with VIEW ERR from the MANUAL Mode<br />

Menu or from NORMAL Mode Menu. The VIEW ERR menu item allows you to<br />

read the current status information.<br />

To clear the error messages:<br />

1. Press * at CLR ERR on either the MANUAL or NORMAL mode<br />

menus.<br />

2. Exiting from the VIEW ERR menu returns the previous menu.<br />

Table 11 Error Messages<br />

LCD Description Action Cause<br />

RESET<br />

Reset occurred due to command or power up. Always present after<br />

power up.<br />

Warning<br />

Normal operation on<br />

power up always sets<br />

RESET. RESET is sent<br />

by HART<br />

communications. Use<br />

CLEAR ERR to remove<br />

warning<br />

LOW POWER Input current < 3.6 mA Takes the device to<br />

low power<br />

ACT ERR Positioner unable to position a valve normally Warning<br />

AIR LOW Supply pressure option is configured and supply pressure is < 10<br />

psi (.69 bar, 69 kPa). Otherwise I/P pressure is below 0.8 psi (.05<br />

bar, 5.5 kPa)<br />

Warning<br />

Mechanical or<br />

pneumatic problem<br />

POS ERR<br />

The position error exceeds configured limit for more than<br />

configured time<br />

Warning after T1 and<br />

Failsafe<br />

Pneumatic/ mechanical,<br />

configuration, loose<br />

magnet<br />

KEYBOARD LCD/Button Failure Warning Damaged buttons or<br />

LCD electronics<br />

MARGN PWR<br />

Input signal is insufficient to proceed<br />

CALIB ERR Calibrate failed Warning Invalid values for<br />

current calibration and<br />

input range by HART<br />

commands<br />

STOP ERR Calibration error. Find STOPS was unsuccessful. Warning Configuration,<br />

calibration<br />

TUNE ERR Auto tune failed Warning Mechanical or<br />

pneumatic problem<br />

causes tuning failure<br />

STD DIAG A standard diagnostic procedure failed to complete Warning Pneumatic /<br />

mechanical,<br />

configuration<br />

EXT DIAG An extended diagnostic procedure failed to complete Warning Pneumatic /<br />

mechanical,<br />

configuration<br />