Check Out and Power Up<br />
Operational Checkout<br />
Pushbutton Locks and Configuration-Lock Jumper<br />
Before performing any of these functions with the local display you must first<br />
ensure that the pushbuttons are placed in the unlocked mode using ValVue<br />
2.4 Lite. The positioner ships in the unlocked mode. See<br />
ValVue 2.4 documentation for more details.<br />
The <strong>SVI</strong> <strong>II</strong> AP offers several levels of plant security. It may be desirable, after<br />
initial setup, to lock the pushbuttons so that the <strong>SVI</strong> <strong>II</strong> AP parameters cannot<br />
be inadvertently changed by the buttons. Several levels of software<br />
modifiable pushbutton locks are provided.<br />
Table 9 Pushbutton Lock Security Level<br />
Level<br />
Security Level 3<br />
Security Level 2<br />
Security Level 1<br />
Access<br />
Allow Local Buttons: Buttons on the <strong>SVI</strong> <strong>II</strong> AP are fully enabled.<br />
Lock Out Local Calibration and Configuration: Use the buttons to perform operations<br />
in normal operating mode and manual mode. Do not go to configure or calibrate<br />
mode.<br />
Lock Out Local <strong>Man</strong>ual: Examine variables in normal operating mode but do not put<br />
the valve in manual operating mode. Access to calibrate or configure modes is not<br />
available.<br />
Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0).<br />
Hardware Configuration Lock<br />
Additional security is achieved using the hardware configuration-lock jumper<br />
shown in Figure 21 on page 34. When set to the secure position, by shorting<br />
the two-pin header, configuration and calibration are not possible using the<br />
local interface or any HART communication tool. Pushbuttons, ValVue 2.4 and<br />
HHC 375 are locked out, except to examine configuration, calibration, and<br />
position. This is similar to Security Level 1 shown in the Pushbutton Lock<br />
Security Level table.<br />
37