Check Out and Power Up<br />

Operational Checkout<br />

Pushbutton Locks and Configuration-Lock Jumper<br />

Before performing any of these functions with the local display you must first<br />

ensure that the pushbuttons are placed in the unlocked mode using ValVue<br />

2.4 Lite. The positioner ships in the unlocked mode. See<br />

ValVue 2.4 documentation for more details.<br />

The <strong>SVI</strong> <strong>II</strong> AP offers several levels of plant security. It may be desirable, after<br />

initial setup, to lock the pushbuttons so that the <strong>SVI</strong> <strong>II</strong> AP parameters cannot<br />

be inadvertently changed by the buttons. Several levels of software<br />

modifiable pushbutton locks are provided.<br />

Table 9 Pushbutton Lock Security Level<br />

Level<br />

Security Level 3<br />

Security Level 2<br />

Security Level 1<br />

Access<br />

Allow Local Buttons: Buttons on the <strong>SVI</strong> <strong>II</strong> AP are fully enabled.<br />

Lock Out Local Calibration and Configuration: Use the buttons to perform operations<br />

in normal operating mode and manual mode. Do not go to configure or calibrate<br />

mode.<br />

Lock Out Local <strong>Man</strong>ual: Examine variables in normal operating mode but do not put<br />

the valve in manual operating mode. Access to calibrate or configure modes is not<br />

available.<br />

Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0).<br />

Hardware Configuration Lock<br />

Additional security is achieved using the hardware configuration-lock jumper<br />

shown in Figure 21 on page 34. When set to the secure position, by shorting<br />

the two-pin header, configuration and calibration are not possible using the<br />

local interface or any HART communication tool. Pushbuttons, ValVue 2.4 and<br />

HHC 375 are locked out, except to examine configuration, calibration, and<br />

position. This is similar to Security Level 1 shown in the Pushbutton Lock<br />

Security Level table.<br />

37