Masoneilan Dresser<br />

<strong>SVI</strong> <strong>II</strong> AP <strong>Instruc</strong>tion <strong>Man</strong>ual<br />

Cabling and Interconnection Requirements<br />

Interconnections are made using shielded twisted pair cables. The shield is<br />

connected to ground at one point only. The signal loop is grounded at only one<br />

point in accordance with plant electrical standards. It is customary to ground<br />

the signal at the controller or intrinsic safety barrier. The <strong>SVI</strong> <strong>II</strong> AP is supplied<br />

with two 1/2 inch NPT conduit entries. M20 adapters are available. Internal<br />

and external ground terminals are provided for case grounding requirements.<br />

Install the <strong>SVI</strong> <strong>II</strong> AP in accordance with local and national code in both general<br />

and hazardous area locations. Substitution of components can impair<br />

suitability for use in hazardous locations.<br />

Note:<br />

The internal electronic components are isolated for ground.<br />

Grounding the case is unnecessary for functional purposes.<br />

Grounding the case may be necessary to conform to local codes.<br />

Capacitance vs. Length of Cable for HART<br />

The HART Communications Foundations specifies cable capacitance<br />

requirements to preserve signal strength. Refer to the standards for detailed<br />

calculation methods.<br />

Do not connect a HART modem and a PC to a control circuit unless the<br />

controller is HART compatible or has a HART filter. Loss of control or a<br />

process upset can occur if the controller output circuit is not compatible with<br />

HART signals.<br />

HART Filter Required for Certain Control System Output Circuits<br />

The <strong>SVI</strong> <strong>II</strong> AP is intended for use with all control systems. However, output<br />

circuits of several major DCS systems are incompatible with the tones used<br />

for HART signals. You must verify that the DCS or controller works reliably<br />

with the HART protocol. When the DCS is incompatible an external HART filter<br />

must be installed between the field wiring and the output card. MTL<br />

manufactures the HART filter HCU16AO. It is a 16 channel DIN rail mounted<br />

device composed of passive circuitry that introduces negligible voltage drop.<br />

For additional information, contact MTL.<br />

Note:<br />

A control circuit must be HART compatible or have a HART filter<br />

installed. Contact the manufacturer of the controller or DCS. See<br />

“HART Filter Requirements” on page 85. of this manual for more<br />

information<br />

74