Using the Digital Interfaces<br />

Display Menus<br />

Table 11 Error Messages<br />

LCD Description Action Cause<br />

CMD STOP HART command aborted Warning Bad data range or data<br />

limitation<br />

BIAS ERR Position algorithm error in output bias Warning Pneumatic/ mechanical<br />

I/P LIMIT I/P current too high or too low Warning Electronic hardware<br />

TEMP ERR Internal circuit temperature high (>80 deg. C, 176 deg. F) or low (120 psi (8.28 bar, 828<br />

kPa)<br />

Temperature compensated pressure sensor 4 reading is outside<br />

the range or pilot pressure recorded is >120 psi (8.28 bar, 828<br />

kPa)<br />

Temperature compensated pressure sensor 5 reading is outside<br />

the range<br />

Warning<br />

Warning<br />

Warning<br />

Warning<br />

Warning<br />

NVM ERR-W Writer to FRAM fails or data repairing in FRAM fails Warning<br />

IRQ FAULT<br />

Valid hidden record (in RAM) existing upon reset that indicates that<br />

an illegal interrupt occurred<br />

Warning<br />

DATA ERR Internal software error data overrun Failsafe CPU/firmware<br />

MCU ERR 1 Micro-Controller Self Check failed Failsafe<br />

SW ERR Software self check error Failsafe CPU/firmware<br />