RS485 option board<br />
Additional notes<br />
- Consider terminating the two furthest ends of the bus to match the transmission line<br />
impedance. A 120 resistor is commonly used, but ideally the line impedance should be<br />
matched to each individual installation. The product is fitted with an internal 120 resistor,<br />
which can be connected to the Rx terminals by setting SW1 - 1 to ON (Figure 23).<br />
- Termination for short lengths of cable should not be necessary < 300 m (< 1 000 ft) @<br />
9 600 Baud.<br />
- Twisted pair cable should not be required for short lengths of cable < 1.5 m (< 5 ft). Standard<br />
screened cable should suffice.<br />
ON<br />
Fig. 23 SW1<br />
1 2 3 4<br />
OFF<br />
Two-wire installation<br />
- Set SW1 - 2 and SW1 - 3 to ON (Figure 24).<br />
- Use an EIA RS485 screened single twisted pair communication cable (e.g.: Alpha wire<br />
part 6412).<br />
- Connect TBK1 - 1 to Master +Tx or +Rx.<br />
- Connect TBK1 - 2 to Master -Tx or -Rx.<br />
- See Figure 26, for a typical installation.<br />
ON<br />
Fig. 24 SW1<br />
1 2 3 4<br />
OFF<br />
Four-wire installation<br />
- Set SW1 - 2 and 3 to OFF (Figure 25).<br />
- Use an EIA RS 485 screened double twisted pair communication cable (e.g.: Alpha wire,<br />
part 6413).<br />
- Using one twisted pair connect: - TBK1 - 1 to Master +Rx<br />
- TBK1 - 2 to Master -Rx<br />
- Using the other twisted pair connect: - TBK1 - 4 to Master +Tx<br />
- TBK1 - 3 to Master -Tx<br />
- See Figure 27, for a typical installation.<br />
ON<br />
Fig. 25 SW1<br />
1 2 3 4<br />
OFF<br />
IM-P333-25 MI Issue 2 25