6.7.3 Pulse output<br />

This sub-menu allows the pulsed output to be configured. The pulse output is a volt free digital<br />

pulse output R≥10 KΩ, Maximum voltage 28 Vdc.<br />

No/Pulse<br />

This allows the total volume, which is equivalent to one pulse to be configured. Units are<br />

dependent on the Unit setting.<br />

Pulse width<br />

This allows the width of the pulse to be set. The width can be set in 0.01 second increments<br />

from 0.02 seconds to a maximum of 0.2 seconds.<br />

Commissioning mode<br />

• Outputs<br />

• Pulse<br />

Commissioning mode<br />

• Outputs<br />

• Pulse<br />

• No/pulse<br />

Commissioning mode<br />

• Outputs<br />

• Pulse<br />

• No/pulse<br />

0001<br />

ok<br />

Commissioning mode<br />

• Outputs<br />

• Pulse<br />

• Width S<br />

Commissioning mode<br />

• Outputs<br />

• Pulse<br />

• Width S<br />

0.02<br />

ok<br />

After the data has been entered, exit the Pulse output sub-menu by pressing .<br />

The menu will then step to Comms output (see Section 6.7.4).<br />

IM-P333-25 MI Issue 2 55