6.5.5 Commissioning sequence for the Linear flowmeter<br />
Linear devices are any device that outputs a linear 4-20 mA output. Note the <strong>M800</strong> when<br />
selected to accept a linear output will not density compensate the signal and various menu<br />
screens will not be shown.<br />
Note: By selecting a Linear flowmeter various menu screens will be disabled, such as the<br />
pressure and temperature inputs.<br />
Commissioning mode<br />
• Meter type<br />
ok<br />
Linear<br />
Commissioning mode<br />
• Meter type<br />
• Linear<br />
• Set 4 mA<br />
Commissioning mode<br />
• Meter type<br />
• Linear<br />
• Set 4 mA<br />
0000<br />
ok<br />
For flow enter<br />
(Nm³/ h or scfm)<br />
Commissioning mode<br />
• Meter type<br />
• Linear<br />
• Set 20 mA<br />
Commissioning mode<br />
• Meter type<br />
• Linear<br />
• Set 20 mA<br />
19999<br />
ok<br />
After the data has been entered, exit the Linear sub-menu by pressing .<br />
The menu will then step to Outputs (see Section 6.7).<br />
IM-P333-25 MI Issue 2 45