21.07.2014 Views

M800 Gas Flow Computer - Spirax Sarco

M800 Gas Flow Computer - Spirax Sarco

M800 Gas Flow Computer - Spirax Sarco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6.7.2 Optional 4-20 mA outputs<br />

Note: If a linear input type flowmeter is selected then these menus do not appear.<br />

The sub-menus, 6.7.1.1 and 6.7.1.2 refer to the optional 4-20 mA outputs from the <strong>M800</strong>, which<br />

can be fitted and configured for either retransmission of temperature or pressure. If these<br />

optional outputs are not fitted then the relevant sub-menus will not appear.<br />

Each output is configured in the same way and can either be set to give a 4-20 mA output of<br />

pressure or temperature.<br />

Check 4 mA<br />

This allows the 4 mA value to be re-calibrated. A digital ammeter / multimeter should be<br />

connected in series with the 4- 20 mA output. Pressing the right arrow button will<br />

display OP = 4 mA and the <strong>M800</strong> will output a steady 4 mA. If the multimeter does not read<br />

4 mA the up and down arrow buttons can be pressed to alter this current<br />

until 4 mA exactly is indicated. Pressing the 'OK' button confirms the setting.<br />

Check 20 mA<br />

This allows the 20 mA value to be re-calibrated. A digital ammeter / multimeter should be<br />

connected in series with the 4- 20 mA output. Pressing the right arrow button will<br />

display OP = 20 mA and the <strong>M800</strong> will output a steady 20 mA. If the multimeter does not read<br />

20 mA the up and down arrow buttons can be pressed to alter this current<br />

until 20 mA exactly is indicated.<br />

Pressing the 'OK' button confirms the setting.<br />

52<br />

IM-P333-25 MI Issue 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!