6.8.3 Testing the 4-20 mA outputs<br />

This allows the 4-20 mA outputs to be tested. Editing the value and pressing the 'OK' button<br />

can set the output to the selected current output. This current will continue to be transmitted<br />

for ten minutes unless the cancel option is chosen. The 4-20 mA output can be set for the<br />

flow, pressure and temperature depending on the options fitted.<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• <strong>Flow</strong><br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• <strong>Flow</strong><br />

04.00 mA<br />

ok<br />

Note: If a linear input<br />

type flowmeter is<br />

selected or no 4-20<br />

mA option board is<br />

fitted then these<br />

menus do not appear.<br />

<br />

<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• Temp<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• Pres<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• Temp<br />

04.00 mA<br />

Commissioning mode<br />

• Test<br />

• 4-20 mA out<br />

• Pres<br />

04.00 mA<br />

ok<br />

ok<br />

After the data has been entered, exit the 4-20 mA output test by pressing .<br />

The menu will then step to Testing the pulse output (see Section 6.8.4).<br />

6.8.4 Testing the Pulse output<br />

This allows the pulsed output to be tested. By selecting 'ON' or 'OFF' the desired test state<br />

of the pulsed output can be selected. Once the 'OK' button is pressed the pulsed output will<br />

remain in the selected state for ten minutes or until the cancel option is chosen.<br />

Commissioning mode<br />

• Test<br />

• Pulse Out<br />

Commissioning mode<br />

• Test<br />

• Pulse Out<br />

On<br />

ok<br />

Commissioning mode<br />

• Test<br />

• Pulse Out<br />

Off<br />

ok<br />

IM-P333-25 MI Issue 2 61