6.7.2.2 Optional 4-20 mA pressure output<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Set 4 mA<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Set 4 mA<br />
000.00<br />
ok<br />
Enter pressure<br />
(bar g or psi g)<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Set 20 mA<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Set 20 mA<br />
3.00<br />
ok<br />
Enter pressure<br />
(bar g or psi g)<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Check 4 mA<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Check 4 mA<br />
op = 4 mA<br />
ok<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Check 20 mA<br />
Commissioning mode<br />
• Outputs<br />
• 4-20 mA Pres<br />
• Check 20 mA<br />
op = 20 mA<br />
ok<br />
After the data has been entered, exit the 4-20 mA output sub-menu by pressing .<br />
The menu will then step to Pulse output (see Section 6.7.3).<br />