Commissioning Error messages<br />

Error message Cause Action<br />

Beta < min<br />

Beta > max<br />

The beta ratio (d/D) for the orifice plate<br />

is less than 0.1<br />

The beta ratio (d/D) for the orifice plate<br />

is greater than 0.75<br />

The pipe diameter is less than 50 mm,<br />

but greater than 12.5 mm.<br />

This is a warning as the pipe size is now<br />

Pipe dia < ISO min below the limits of the ISO standard,<br />

however calculation is still possible<br />

following the guidelines within<br />

the standard.<br />

Pipe dia > max<br />

The pipe diameter is greater than<br />

the maximum of 1000 mm<br />

Check that the sizing<br />

of the orifice is correct<br />

Check that the sizing<br />

of the orifice is correct<br />

The warning can be<br />

cancelled by pressing<br />

the OK button.<br />

The application is outside<br />

of the <strong>M800</strong> limits.<br />

IM-P333-25 MI Issue 2 71