Symptom<br />

2<br />

Display flashes<br />

Action<br />

1. Remove power from the flow computer<br />

2. Disconnect all option modules and plugs (except the mains).<br />

3. Reapply power to the flow computer<br />

ELSE:<br />

IF: The flow computer still exhibits the same fault THEN:<br />

3.1. The product is faulty and should be replaced<br />

on and off 4. Methodically replace each plug / module until the fault occurs.<br />

(1 second 5. Investigate and rectify any faults in the wiring, external sensor/<br />

approximately)<br />

transducers and modules associated to that plug.<br />

Explanation:<br />

The internal power supply is unable to power up. If the voltages<br />

cannot be generated, the power supplies switches off for<br />

approximately 1 second. The power supply then attempts to<br />

power up again. If the fault is still present, the cycle is repeated<br />

until the fault is rectified. This is a safety feature and does not<br />

permanently damage the product.<br />

3<br />

Product powers<br />

up for a period<br />

of time (greater<br />

than 1 minute),<br />

then switches<br />

off<br />

4<br />

Clock and<br />

calendar keeps<br />

resetting<br />

5<br />

Error message<br />

displayed<br />

1. Monitor the mains supply and ensure it is continuous<br />

and within the specified limits.<br />

2. Measure the ambient temperature and ensure it is less<br />

than specified.<br />

3. Investigate symptom 2.<br />

Explanation: A resetable thermal cut out device will operate if<br />

one or more of the following occur:<br />

- The power drawn exceeds the specification,<br />

- The input mains voltage is less than specified,<br />

- The ambient temperature is greater than specified. The<br />

internal power supply will switch off until the product's<br />

internal temperature drops to below 65°C. This is a safety<br />

feature and does not permanently damage the product.<br />

1. Ensure the product is powered up for 24 hours.<br />

2. Replace battery (See Section 8 'Maintenance').<br />

1. Commissioning Error messages (see page 71).<br />

2. Operational Error messages (see page 72).<br />

70<br />

IM-P333-25 MI Issue 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!