Basic safety instructions<br />
2.4 Safety functions of the fail-safe processing unit<br />
The F-Host, to which the measuring system is connected, must perform the following<br />
safety checks.<br />
To enable the correct measures to be taken in case of measure, the following<br />
applies:<br />
If no safe position can be output due to an error detected by the measuring system,<br />
the PROFIsafe data channel is automatically put into fail-safe status. In this status<br />
so-called "passivated data" are output via PROFIsafe. Also see the chapter<br />
"Output of passivated data (substitute values) in case of error" on page 183.<br />
Passivated data are:<br />
– PROFIsafe data channel: all outputs are set to 0<br />
– PROFIsafe status: error bit 2 1 Device_Fault is set<br />
– PROFIsafe-CRC: valid<br />
Upon receipt of passivated data, the F-Host must put the system into a safe<br />
state. It is only possible to leave this error state by eliminating the error and<br />
then switching the supply voltage off and on again!<br />
The process data channel addressable via PROFIBUS is not necessarily affected<br />
by this. If the internal diagnosis in the master channel does not detect an error, the<br />
process data are still output. However, these data are not safe for the purposes of a<br />
safety standard.<br />
2.4.1 Mandatory safety checks / measures<br />
Measures for commissioning, changes<br />
F-Host error reaction<br />
Application-dependent parameterization and definition of the<br />
necessary iParameters, see chapter "iParameters" on –<br />
page 159.<br />
In the event of parameter changes, check that the measure<br />
STOP<br />
is executed as desired.<br />
Check by F-Host<br />
Cyclical consistency check of the current safety-oriented<br />
data in the <strong>TR</strong>-PROFIsafe module in relation to the<br />
previous data.<br />
Travel curve calculation and monitoring by means of cyclical<br />
data in the <strong>TR</strong>-PROFIsafe module.<br />
Monitoring of cyclical data in the <strong>TR</strong>-PROFIsafe module,<br />
and the process data in the <strong>TR</strong>-PROFIBUS module.<br />
Timeout: Monitoring of the measuring system - response<br />
time. For checking e.g. cable breakage, power failure etc.<br />
F-Host error reaction<br />
STOP<br />
STOP<br />
Receipt of passivated<br />
data --> STOP<br />
STOP<br />