PROFIBUS / PROFIsafe - Commissioning<br />

6.4 Start-up on PROFIBUS<br />

Before the measuring system can be included in the user data traffic<br />

(Data_Exchange), the master must first initialize the measuring system during startup.<br />

The resulting data traffic between the master and the measuring system (slave) is<br />

divided into the parameterization, configuration and data transfer phases.<br />

It is checked whether the planned nominal configuration agrees with the actual device<br />

configuration. The device type, the format and length information as well as the<br />

number of inputs and outputs must agree in this check. The user is thus reliably<br />

protected against data format errors.<br />

If the check was successful, there is a switch to the DDLM_Data_Exchange mode. In<br />

this mode the measuring system transfers e.g. its actual position.<br />

Figure 16: DP slave initialization<br />