Troubleshooting and Diagnosis Options<br />
11 Troubleshooting and Diagnosis Options<br />
11.1 Optical displays<br />
For assignment and position of the status LEDs see chapter "Bus status display" on<br />
page 145.<br />
11.1.1 LED, green<br />
Green LED Cause Remedy<br />
Off<br />
Power supply absent<br />
Hardware error,<br />
measuring system defective<br />
Check power supply, wiring<br />
Replace measuring system<br />
3x 5 Hz<br />
repeating<br />
− Measuring system could not<br />
synchronize with the F-Host in<br />
the start-up phase and<br />
requests a reintegration<br />
− An error in the safety-oriented<br />
communication or a<br />
parameterization error was<br />
detected, and has been<br />
eliminated<br />
For reintegration of the measuring system a user<br />
acknowledgement with positive edge of variable<br />
ACK_REI of the F-Periphery-DB is required, see<br />
chapter "Passivation and reintegration of the<br />
measuring system" on page 188<br />
1 Hz<br />
F-Parameterization defective, e.g.<br />
incorrectly set PROFIsafe<br />
destination address F_Dest_Add<br />
− Check PROFIBUS address set with the<br />
hardware switch. The address set here gives the<br />
necessary PROFIsafe destination address +<br />
500, see chapter "Bus addressing" on page 136<br />
− Synchronize required safety class F_SIL of<br />
system and measuring system, see chapter<br />
"F_SIL" on page 155<br />
on<br />
Measuring system ready for<br />
operation,<br />
connection established with<br />
PROFIBUS master<br />
–<br />